Chromalox SRL 10-1CR.SRL Self-Regulating Low Temperature
• Self-Regulating, Energy Efficient
• 16 AWG Buss Wire
• Circuit Lengths to 660 Feet
• Process Temperature Maintenance to 150°F (65°C)
D
E
C
B
Maintains up to 150°F Withstands up to 185°F
Low Tempera- ture
A
Temperature
Self Regulating Output
• Maximum Continuous Exposure Features
Temperature, Power Off, 185°F
(85°C)
• Energy efficient, self-regulating SRL uses less energy when less heat is required.
• Industrial Freeze Protection
• Easy to install, SRL can be cut to any length Applications
(up to max. circuit length) in the field.
E
High Temperature Fluoropolymer or TPR Overjacket (optional) — Corrosion resistant, flame retardant overjacket is highly effective in many environments. TPR coatings protect against certain inorganic chemical solutions. Fluoropolymer coatings are used for exposure to organic or corrosive solutions. These coatings also protect against abrasion and impact damage.
• Freeze Protection of Fire Protection System Piping
• Field Splicing Without Disrupting Heat Output
• 3,5,8and10W/Ft.
• 120 and 208 - 277 Volt From Stock
• Approximate Size 3/8”W x 1/8"H
• Min. Bend Radius 1-1/8"
• For Use on Metal and Plastic Pipes
Description
Chromalox SRL self-regulating heating cable provides safe, reliable heat tracing for freeze protection of pipes, valves, tanks and similar applications. Constructed of industrial grade 16 AWG buss wire with a tinned copper braid and optional overjacketing, SRL ensures op- erating integrity in Div. 2 hazardous environ- ments as well as certain corrosive industrial environments. SRL heating cable
has a maximum maintenance temperature rating of 150°F (65°C).
WARNING — A ground fault protection device is required by NEC to minimize the danger of fire if the heating cable is damaged or improp- erly installed. A minimum trip level of 30mA is recommended to minimize nuisance tripping.
• Field splices can be performed easily in min- utes with no scrap or wasted cold sections.
• SRL features lower installed cost than steam tracing, less maintenance expense and less downtime.
Approvals
ATEX and IECEX Exe IIGb, Factory Mutual (FM) Approved for ordinary areas. UL Listed, CSA Certified for ordinary areas. UL listed for freeze protection of fire protection system piping. FM Approved for hazardous (classified) areas when used with U Series, DL and EL accessories:
• Class I, Div. 2, Groups B, C, D (gases, vapors)
• Class II, Div. 2, Groups F, G (combustible dust)
• Class III, Div. 2
(easily ignitable fibers and fillings)
• 3 Watt Rated T6 Temperature Class
• 5 and 8 Watt Rated T5 Temperature Class • 10 Watt Rated T4A Temperature Class.
CSA Certified for hazardous areas when used with DL, EL or U Series accessories:
• Class I, Div. 2, Groups A, B, C, D • Class II, Div. 2, Groups F, G.
• ATEX and IECEX Exe IIGb
• IIG Exe II
Cut to Length in Field
Can be Single Overlapped
• SRL can be overlapped without burnout, which simplifies heat tracing of in-line pro- cess equipment such as valves, elbows and pumps.
• Because SRL is self-regulating, over-temper- ature conditions are minimized.
• Chromalox termination, splice, tee and end seal kits reduce installation time.
Construction
A Twin 16 AWG Copper Buss Wires — Provide reliable electrical current capability.
B Semiconductive Polymer Core Matrix — “Self-Regulating” component of the cable, its electrical resistance varies with temperature. As process temperature drops, the core’s heat output increases; as process temperature rises, the heat output decreases.
C Polyolefin Jacket — Flame retardant, electrically insulates the matrix and buss wires and provides resistance to water and some inorganic chemical solutions.
D Tinned Copper Braid — Provides additional mechanical protection in any environment and a positive ground path.
Output
G-10
Heating Cable
SRL
Self-Regulating Low Temperature (cont’d.)
Thermal Output Ratings on Insulated Metal Pipe1
14 13 12 11 10
9
8
7
6
5
4
3
2
1
0 10 20 30 40 50 60 70 80 90100110120130140150
Pipe Temperature (°F)
Note 1 — Thermal output is determined per IEEE 515-2004 Standard for testing, design installation, and maintenance of electrical resistance heat tracing section 4.1.11 Method C.
Thermal Output Ratings on Plastic Pipe with Aluminum Tape
9
8
7
Heat Output (W/Ft.) Heat Output (W/Ft.) 6
5
S
4
3
2
1
0 10 20 30 40 50 60 70 80 90100110120130140150 Pipe Temperature (°F)
Output Wattage at Alternate Voltages (W/Ft.)
Heating Cable
10 W/Ft.
8 W/Ft.
5 W/Ft.
3 W/Ft.
Cable Output vs. Temperature
SRL3
SRL10
RL5
SRL8
Cable Output vs. Temperature
Model
SRL 3 SRL 5 SRL 8 SRL 10
2.4 4.1 6.88 8.7
-20 2.6 -13 3.4 +15 -18 4.5 -10 5.6 +13 -14 7.28 -9 8.96 +12 -13 9.2 -8 11.1 +10
208V
% Change In Output
220V
% Change In Output
277V
% Change In Output
self-regulating
Circuit Breaker Selection (Max. Circuit Lengths in Ft.)
Cable Rating
50°F Start-Up (Ft.)
50°F Start-Up (Ft.)
0°F Start-Up (Ft.)
0°F Start-Up (Ft.)
-20°F Start-Up (Ft.)
-20°F Start-Up (Ft.)
10A
15A
20A
25A
30A
40A
10A
15A
20A
25A
30A
40A
10A
15A
20A
25A
30A
40A
330 360 NR 120 185 245 300 360 NR SRL3-1C 205 305 360 NR NR NR 135 200 270
660 NR NR 245 370 495 600 660 NR SRL3-2C 400 600 660 NR NR NR 275 415 555
225 270 NR 80 120 160 205 245 270 SRL5-1C 125 185 250 270 NR NR 90 135 180
450 540 NR 160 245 325 405 490 540 SRL5-2C 250 375 505 540 NR NR 180 270 360
180 215 NR 65 100 130 165 200 210 SRL8-1C 100 150 200 215 NR NR 70 110 145
335 395 420 120 175 235 300 350 420 SRL8-2C 185 285 375 420 NR NR 135 200 265
SRL10-1C 60 95 130 160 180 NR 50 80 105
130 155 180 45 70 95 120 140 180 SRL10-2C 100 160 210 260 315 360 80 125 170 210 255 340 75 120 160 195 240 320 NR = Not Required. Maximum circuit length has been reached in a smaller breaker size.
Note — Thermal magnetic circuit breakers are recommended since magnetic circuit breakers could "nuisance trip" at low temperature. G-11
SRL
Self-Regulating Low Temperature (cont’d.)
Ordering Information
Output (W/Ft.)
Volts
Model
Stock
PCN
Wt./1000' (Lbs.)
3 @ 50°F
120
SRL 3-1C SRL 3-1CT SRL 3-1CR
S
382678
383400
382731
53 66 64
208 - 277
SRL 3-2C SRL 3-2CT SRL 3-2CR
S
382686
383419
382740
53 66 64
5 @ 50°F
120
SRL 5-1C SRL 5-1CT SRL 5-1CR
S
382694
383443
382758
53 66 64
208 - 277
SRL 5-2C SRL 5-2CT SRL 5-2CR
S
382707
383451
382766
53 66 64
8 @ 50°F
120
SRL 8-1C SRL 8-1CT SRL 8-1CR
S
382555
383460
382598
53 66 64
208 - 277
SRL 8-2C SRL 8-2CT SRL 8-2CR
S
382563
383478
382600
53 66 64
10 @ 50°F
120
SRL 10-1C SRL 10-1CT SRL 10-1CR
S
382820
383486
382846
53 66 64
208 - 277
SRL 10-2C SRL 10-2CT SRL 10-2CR
S
382838
383494
382854
53 66 64
To Order — Specify length, model, PCN and installation accessories.
Accessories
Power Connection Heat trace to electrical service connection
UPC RTPC UMC RTST UES RTES USL RTST-SL UAS RTAS UBC RTBC
SSK RT-RST RT-RES N/A THL/TXL THR/TXR
Accessories
U Series
DL
EL
Splice & Tee
End Seal
Lighted End Seal Thermostat
Ordering Information
To Order —
Complete the Model Number using the Matrix provided.
Contact your Local Chromalox Sales office for monitor wire option.
For terminating cable
Ambient air sensing thermostat
Line sensing mechanical thermostat
Model Self-Regulating Low Temperature
SRL
Self-Regulating, Low Temperatue Heating Cable
Code
3 5 8 10
Output (W/Ft.)
Three Five Eight Ten
Code Voltage
1 120
2 208 - 277
Code Braid and Overcoat Options
More Information
is Available Online
C Tin-Plated copper metallic braid for additional protection and ground path
CT Fluoropolymer corrosion resistant overjacket over braid for hostile/corrosive environments
CR TPR overjacket over braid for protection against certain inorganic chemical solutions
C Typical Model Number
on Heat Trace. Bookmark Your Browser to
www.chromalox.com and Select Manuals.
SRL
5 1
To Order — General Application & Installation Accessories such as tape, pipe straps, warning labels, etc., refer to the U Series, DL & EL General Application Accessories page at the end of this section.